Introduction
Our company is a new technology enterpriseengaged in intelligent motor protector of scientific research, production, sales and technical support, which has in-depth research on the protection of the motorThe motor protector of our company possess those advantages of low price, good quality, great variety of goods, are deeply loved by users.Our comprehensive intelligent motor protectors which adopt advanced 16-bit single chip microcomputer and controller of MICRHIP Company in USA as well as low power consumptionintegrated circuit as the core,provided with complete protection function, Intuitive measuring parameters, sensitive reaction,stable and reliable in work, high measuring accuracy, simple protection parameter setting and digitization,intelligentizationand networking etc.,can satisfy the requirements of different users.Our products are widely used in electric power, petroleum, metallurgy, chemical, mining, cement, textile and other industrial motor and three-phase power system, to protect the following situations: overheating, overload, underload, overvoltage, undervoltage, phase, locked-rotor, leakage, unbalanced three-phase circuit protection,The protector can also form network system combined with PLC, DCS and backstage unit through communication interfaceRS - 485andanalog output interface 4-20mA and through the backstage unit to protect the device parameters modification and operation control. The protector is a kind of artificial intelligence instrument and high-tech productsimproving safety and automation management level of motor, can form remote monitoring with PC communications.
Basic Protection Function
Starting protection: In the process of starting, only provides protection with overvoltage, undervoltage, short circuit, phase and three-phase unbalanced, start overtime without overcurrent.
Over voltage protection: When working voltage of protector exceed the set voltage for 6 seconds(default value is 260V).
Low voltage protection:When working voltage of protector is lower than the set voltage for 6 seconds(default value is 180V)
Open-phase protection:Any phase current of the motor is power off , protector will perform in 2 seconds.
Motor Shaft Lock Protection:When running current exceeds set multiple,protector will perform in 2 seconds.(default value is 4 times)
Leakage protection:When leakage current value is detected to exceed the set value by zero sequence current transformer, protector will perform in 1 second.
Short-circuit protection: When short-circuit current exceed leakage current 5 times, protector will perform in 2 seconds.
Unbalance protection:When current value difference between any two phases exceeds set percentage,protector will perform in 2 seconds.
Underflow protection: When running current is lower than set undercurrent threshold,protector will perform in 5 seconds.(default value is 0)
Overflow protection: When running current is greater than the set current value, the action time of the over-current protection turns to inverse time protection or quick break protection.
Self-start::The protector requires the user to set the start time with this function, the motor does not start communications at this time.(default value 0 is closed )
Start timeout protection:When motor start current after delay time exceeds the overflow current value(default value is 4s)
Contact capacity:AC220V/5A AC380V/3A Electrical endurance≥105次。
Contact characteristics:contact J1 close, contact J2 open, contactJ3 programming output(Be subject to shell wiring diagram)
Communication interface:SDI RS485, shielded wire, communication distance ≤1200m
Permissible error:±5%
Fission display:500cm distance less than 500cm standard configuration 80cm
Matching function:Under 200A no need to configure the transformer, more than 200 a protector need to configure 3 standard transformer 5A. For example, 400A specification needs with 400A/5A current transformer.
Communication protocol: Support self-programmed and MODBUS and various kinds of communication protocol.
Current output: Three phase current average turns into DC4-20mA signal.
Sheet 1 (time/unit/second)
Serial No
multiple time
|
0
|
1
|
2
|
3
|
1.1
|
5
|
60
|
120
|
180
|
1.2
|
5
|
50
|
100
|
150
|
1.3
|
5
|
35
|
70
|
100
|
1.5
|
5
|
10
|
20
|
30
|
2.0
|
5
|
6
|
11
|
15
|
3.0
|
5
|
3
|
5
|
7
|
4.0
|
5
|
2
|
3
|
4
|
Note:1、It’s advisable that transformer is fixed at the bottom of the a.c. Contactor, using screws and standard 35 mm rail installation; Three-phase line respectively go through the transformer three holes; Connect the second line according to the shell wiring diagram and check before electricity debugging.
2、AC power of protector itself should be connected ahead of the a.c. Contactor to guarantee power supply for a long time.
Typical Application Of Wiring Diagram
Installation Dimensions
Current Transformer
Protection device in the specification which is less than 200A and 200A does not need to match current transformer (thread) at a time, when the current specification is more than 200 a need to match three standard than current transformer, the two side outlet end of the standard current transformer, respectively, through the protection of the corresponding current transformer hole (secondary thread).
Typical Application Diagram
Product selection
product name
|
product model
|
basic function
|
remarks
|
Motor protector
|
CHTK100H
|
|
Economical electric motor protector
Split type and one-piece type
|
Guide rail installation or open hole
installation 91mm * 44mm
|
CHTK310H
|
|
Conventional intelligent electric
motor protector
Split type and one-piece type
|
CHTK500 enough functional motor
protector with start button
|
|
Blocking rotation, phase breaking,
overcurrent, three-phase current imbalance, overvoltage, undervoltage, short
circuit, leakage and other fault protection, three-phase current measurement,
display the working voltage
|
Open hole is 92mm * 66mm
|
CHTK600H high-end motor protector
|
|
Overcurrent, blocking, phase breaking,
three-phase current
Unbalanced overvoltage, undervoltage,
short circuit, leakage (optional) and other fault protection, phase current,
phase voltage, line voltage frequency, active power, reactive power, power
factor measurement multi-channel switch quantity signal
|
Open hole is 77mm * 55mm
|
CHTK800H high-end motor protector
|
|
Open hole is 90mm * 90mm
|