Loading...

  •  

Universal Microcomputer Measurement and Control Device



Real-Time Data Measurement



The comprehensive protection device adopts a new and improved measurement technology and has a powerful vectorization operation function. Due to different digital processing of various analog values, the fundamental wave quantity, high frequency component and DC component are effectively separated, eliminating the need for The influence of offset and noise on the measurement accuracy can effectively compensate the decay of the signal measurement element, which ensures the long-term, stable and reliable operation of the device in various harsh environments.
¡ø la, lb, lc protection current (measured);
¡ø UAB, UBC, UCA three-phase line voltage (measured);
¡ø 10 zero sequence current (measured);
¡ø 3UO zero sequence voltage (measured);
¡ø The sampling element adopts precision voltage and current transformer, which is small in size, light in weight and small in load;
¡ø Using high-speed and high-precision DSP microprocessor, which can quickly process the 9th harmonic;

Control Output

¡ø Close relay;
¡ø Opening relay;
¡ø Protection relay;
¡ø Accident warning relay;
¡ø Event alarm relay;
¡ø 2 remote control relays;
¡øOptional independent anti-jump circuit without opening and closing current requirements;

Binary Input

¡ø 10-channel passive switch input isolated by photoelectric coupling element;
¡ø The unique anti-shake filtering algorithm eliminates the misjudgment caused by debounce and instantaneous spark interference;

Digital Relay Output

¡ø The jumping and closing relay can be selected by software and external connection, switch on and off,
¡ø The signal relay can be flexibly configured to hold or pulse jog output;

Friendly Man-Machine Interface

¡ø The comprehensive protection arm is equipped with a dot-matrix 128*64, high-contrast blue-white-white graphic LCD display;
¡ø Similar to the full Chinese menu operation of the WIN interface, it can display system parameters such as simulation, primary system diagram, measurement data, switch status, real-time data, event records, protection settings, etc.
¡ø The flexible texture button is used to select the screen menu and drive, switch the data screen and set the fixed value. The interface operation will not have any impact on the system operation. The fixed value modification is password protected.
¡ø Through the bus interface, it can be connected with the PC to realize the programming of more parameters;
¡ø Main working conditions of monitoring, self-diagnosis and equipment circuit,
¡ø The internal abnormality of the device (data, fixed value, storage components, ports, communication) is reported;
¡ø PT disconnection alarm;

SOE Events

Display and save the most recent event records. If a new fault occurs, it can describe the fault of the system and the response of the protection device in detail. The details of the event record include:
¡ø Record fault trip, event alarm, etc.;
¡ø Resolution 2ms, power-off hold;

Communication

Supported communication interface: RS485;
It can form a geographical span network system through multi-contact network connection. The single line is stable in the RS485 bus mode, stably connecting 64 nodes, the maximum transmission distance is 1200mm, and the maximum speed can reach 9600bps;
¡ø Industrial computer via RS485-RS232 converter, via RS485-fiber converter;
¡ø Communication protocol Modbus-RTU;


Product Technical Specifications And Citations



2.1, environmental conditions

Work temperature range -10---+55¡ãC
Relative humidity 45---80% permanent 95% no condensate haze in a short time
Atmospheric pressure 80--- 110kpa
Altitude <2000m
Storage and transportation temperature range -40---+75'C


2.2, power

 

DC power supply

Rated voltage

220V DC (110V)

Perpetual scope

100---250V
AC power

Rated voltage

220V AC

Perpetual scope

150---250V
Power consumption

normal

<3W/VA

action

<10W/VA
power drop

50%

1 s

0%

100ms


2.3, protect AC signal input

current Rated current In SA (1A)
Power consumption < 0.5VA
Thermal stability continuous 20A
1 s 100A
Dynamic stability 10ms 250A
Voltage Rated voltage Un 100V
limit voltage 200V
Power consumption < 0.3VA


2.4, measure AC signal input

parameter name _ Range

error

Power consumption

phase voltage UAB , UBC , UCA 10 --- 129 V (x PT)

<=05%

< = 0.3VA

Three-phase current la , le 0 . 2 --- 6A(x CT)

<=05%

< = 0.3VA

Power factor PF 0.5L --- 0.5C _ _ _

<=05%


2.5, Open into the basin signal input

 

Passive contact signal input

Number of signal sheaths 10 way
The scope of work 24V DC (the device is self-produced)
self-consumption power <0.3W
Resolution 2 ms Pulse frequency <100 Hz


2.6, mechanical properties and structure

Package Size (H)/(W)/(D) mm (for reference only)
Device size (H)/(W)/(D) mm (for reference only)
The most loaded coins Approx. () kgmm (for reference only)
shell material Aluminum profile structure
Protection class IP5YN
Installation method Recessed or tiled, impact-fixed


2.7, open the basin relay output

Maximum switching voltage 250V AC/30V DC
Maximum switching current 8A
Maximum switching power 1250VA/150W
output contact capacity <250V, 1A ( inductive load), breaking capacity <50W
specified load 5A 250V AC/30V DC
medium pressure 4000V AC
Insulation resistance 1000M¦¸


2.8, event record

log event type Fault, event, limit violation, external jumper
Number of events logged 30 Power-down retention
record event content Year, month, day timescale, event type details
Time resolution 2 ms
 

Event query method

remote communication call
Local key menu LCD display


2.9, pass letter catch mouth

 

Electrical Specifications (isolated RS485)

number of communication nodes 64
Transmission rate 4800 --- 9600 Buad
Transmission distance (9600 Buad) 1000 m
Connector Terminal output
  IEC 60870-5-103 8 data bits, 1 stop bit, even parity


2.10, try test Require

Insulation test Insulation resistance 2kv 50Hz 1 minute
frequency withstand voltage IEC60-2 50M¦¸ _ _
Damp heat test IE C60-2-30 50M¦¸ _ _ 1.5kV
Impact withstand voltage test Switch input circuit to ground Earth 5kV
Other circuits IEC255-5 Earth 5kV
Mechanical vibration test Test orientation triaxial
Test frequency range 10 --- 150Hz
crossover frequency f ¨Q 60Hz , constant amplitude 0.075mm _
Frequency sweep cycles per axis f>60Hz ; constant acceleration 10m
IEC255-21 10 / S²


2.11, EMC Electromagnetic Compatibility

Anti-high frequency interference test IEC255-22-1

1M Attenuated Shockwave

common mode 2.5kV
differential mode 1.0kV
Electrostatic discharge interference test  III Class

IEC6100-4-2

contact 6.0kV
Air 8.0kV
Radiated electromagnetic field interference test EN55011 Test field strength  
scanning frequency 150kHz---80MHz
RFI test Reference directly in common mode (IEC6100-4-6) 10V/m (rms) , f=150kHz--- 80MHz
cited in radiation (IEC6100-4-6) 10V/m (rms) , f=80Hz---1000MHz
fast transient test

IEC255-4

Common Mode Voltage Peak Pulse

Frequency

per - polarity duration

2kV 4kV
5kz 2.5kz
10 min
Surge lightning test IEC6100-4-5 Power, AC, DC inlets 4KV common mode
2KV differential mode
I/O Entrance 2KV common mode
1KV differential mode



Installation Notes


Application


Product selection


product name

product model

basic function

remarks

Special microcomputer in the middle cabinet

CHTK800

Microcomputer protection device

The machine protection device can monitor, control and protect the state of the loop through the signals of the measuring elements such as the connected current, transformer, voltage transformer and so on.Such as short-circuit protection, overload protection, single-phase ground protection, and so on.

Open hole is 195mm * 158mm

line protection

CHTK810

breaking protection

Limit speed break protection

Current protection

Load protection

sequence current protection

overvoltage crowbar

undervoltage protection

Three-phase primary reclosing

Speed up after the overlapping gate

Zero order voltage protection

General backlimit protection

Negative order current protection

Start process protection

Unbalanced current protection

Unbalanced voltage protection

Heavy gas protection

Light gas alarm

overtemperature protection

High temperature alarm

Non-power protection

PT off-line alarm

Enter the line for self-investment protection

Segmental protection protection

Open hole is 195mm * 158mm

With the anti-jump of an additional + 100 yuan, with the measurement of another + 100 yuan;

Enter the line for self-investment protection

CHTK811

Transformer protection

CHTK820

motor protection

CHTK830

Capacitor protection

CHTK840

Bus voltage monitoring

CHTK850

Bus line voltage monitoring P and parallel

CHTK851

The parent union section is prepared for self-projection

CHTK860




Online Message

*
*
*

Related Products

See More