Loading...

  •  

Small Current Grounding Line Selection Device


Overview


Small current wire selection device is an integral part of the industrial field circuit protection system, the device can accurately determine the location of the fault when the circuit system occurs grounding (arc or metallic) phenomenon, and the information for remote transmission, so as to facilitate the maintenance of the site personnel.

1.1. Function and characteristics
The structure of the device adopts modular design, and the main controller adopts 16-bit high performance single chip computer with high speed data acquisition module. Among the modules, CAN communication methods with redundant verification and multi-master transmission are used for data exchange and sharing.The panel uses the display screen and a simple 5-key operation function for man-machine dialogue.
The system adopts double watchdog mode to detect the operation of the system; wide working input voltage, high current signal measurement accuracy; fault and setting information memory function; real-time data and fault data remote transmission function.

Model And Parameters And Service Environment


Table 1 of Technical Parameters of Small Current Line Selection Device

Technology, technique, reference, and mark

Technology, technique, reference, and number

Prepare, note

working voltage

AC/DC:85V~265V

Input the opening zero-order voltage, U0x

0~150V

The measurement accuracy is 1%

Enter zero-order current

20mA~3A

The measurement accuracy was 0.5%

Select line range

There are 54 bus routes in 3 sections

It can be set by itself


Key Description

Keys include: menu key, confirmation key, + key, -key and return key.The reset button absorbs the alarm relay after the failure, and press the reset button to remove the alarm.Menu select mobile menu item, press the menu key to select the menu item order move, press confirm to enter the selected menu item.The + keys, and-keys are used to resize the data.The renderings are as follows:


Interface Definition And External Dimensions

Wiring diagram


Interface Definition

terminal A

terminal B

terminal C

terminal D

terminal E

terminal F

terminal G

terminal H

1

AC/DC220V

Standby 1

Current 1 *

Current 10 *

Current 19 *

Current 28 *

Current 37 *

Current 46 *

2

landing

Standby 2

Current 1

Current 10

Current 19

Current 28

Current 37

Current 46

3

AC/DC220V

+24V

Current 2 *

Current 11 *

Current 20 *

Current 29 *

Current 38 *

Current 47 *

4

Alarm open node 1

24V ground

Current 2

Current 11

Current 20

Current 29

Current 38

Current 47

5

Alarm open node 1

Open voltage 1

Current 3 *

Current 12 *

Current 21 *

Current 30 *

Current 39 *

Current 48 *

6

Alarm open node 2

Open voltage 1

Current 3

Current 12

Current 21

Current 30

Current 39

Current 48

7

Alarm open node 2

Open voltage 2

Current 4 *

Current 13 *

Current 22 *

Current 31 *

Current 40 *

Current 49 *

8

Alarm open node 3

Open voltage 2

Current 4

Current 13

Current 22

Current 31

Current 40

Current 49

9

Alarm open node 3

Open voltage 3

Current 5 *

Current 14 *

Current 23 *

Current 32 *

Current 41 *

Current 50 *

10

485 Ground

Open voltage 3

Current 5

Current 14

Current 23

Current 32

Current 41

Current 50

11

RS485-A

Current 6 *

Current 15 *

Current 24 *

Current 33 *

Current 42 *

Current 51 *

12

RS485-B

Current 6

Current 15

Current 24

Current 33

Current 42

Current 51

13

Current 7 *

Current 16 *

Current 25 *

Current 34 *

Current 43 *

Current 52 *

14

Current 7

Current 16

Current 25

Current 34

Current 43

Current 52

15

Current 8 *

Current 17 *

Current 26 *

Current 35 *

Current 44 *

Current 53 *

16

Current 8

Current 17

Current 26

Current 35

Current 44

Current 53

17

Current 9 *

Current 18 *

Current 27 *

Current 36 *

Current 45 *

Current 54 *

18

Current 9

Current 18

Current 27

Current 36

Current 45

Current 54

explain:
1.18 Products E, F, G, H;
2.36 products are G and H.

Overall Dimensions And Hole Dimensions

The opening diagram is as follows, the opening size is 360 * 140; the installation screw opening: diameter 6~7mm.
Chassis depth: 180mm; Panel size: 396 * 148mm

Application




Product selection


product name

product model

basic function

remarks

Small-scale current line selection device

CHTK-DX

One trip can take 18 roads, plus + 600 standard

Bus line in section 3 is 2800 yuan below 18 roads, plus + 20 yuan for each additional road; up to 54 roads



Online Message

*
*
*