Panel And Function Description
Description of the switch status indicator panel:
(Towards: the numbering in the figure is to illustrate the indication function of the layout, and there is no numbering on the actual instrument)
01. Circuit breaker closing indication
02. Circuit breaker opening indication
03.¢Ù, 03¢ÚWorking position indication
04.¢Ù, 04¢ÚTest position indication
05. Grounding switch closed indication
06. Earthing switch sub-indication
07. Energy storage indication
08. Live indication (ABC) three-phase
09. Lockout indication
10. Heating and dehumidification indication
11. Manual and automatic heating switch
12. The first temperature display
13. The first channel humidity display
14. The second temperature display
15. The second humidity display
16.SET: Menu key and OK key
17.◀ Value increase key
18.▶ Value decrease key
Function Description
(1) Circuit breaker status display:
When closing, the closing contact is closed, and the red analog bar 01 lights up.
When opening, the opening contact is closed, and the green analog bar 02 lights up.
(2) Display of handcart position:
When the working position contact is closed, the red vertical analog bar 03 lights up.
When the test position contact is closed, the green horizontal analog bar 04 lights up.
(3) Grounding knife position indication:
The contact is closed, and the red analog bar 05 is on, indicating that the grounding is closed.
The contact is disconnected, and the green analog bar 06 is on, indicating that the grounding is disconnected.
(4) Energy storage status indication:
The contact is closed, and the red light 07 is on, indicating that the energy has been stored.
Note: In the power-off state, all the luminous indications are off, and the above contact signals are all from the auxiliary contacts of the circuit breaker.
(5) High voltage live indication LED starting voltage (KV): bus voltage ¡Á 0.150.65.
Latching start control voltage (KV): busbar voltage ¡Á 0.65.
(6) Temperature and humidity control function:
Number of sensor channels: two channels of condensation + two channels of temperature or one channel of condensation + one channel of temperature.
Logical relationship: start heating when temperature <5¡æ or humidity>90%RH (two-way heating);
Stop heating when temperature>15¡æ or humidity<80%RH;
When the temperature is >45¡æ, the output of the overheat exhaust air relay;
When the temperature is less than 35¡ãC, the overheated exhaust air stops outputting.
Disconnection alarm: The temperature and humidity sensor or heater is disconnected, and the corresponding alarm indicator light is on.
Manual heating switch: The switch can be in two states, automatic or manual, usually in the automatic state. At this time, the temperature and humidity control logic is the same as above. When the switch is pressed, it is in the manual forced heating state.
(When the ambient temperature is lower than 15¡ãC, after the general heating is canceled, the heater will stop heating to 15¡ãC)
(7) Intelligent anti-mistake voice prompt:
When the handcart is between the test position and the working position, when the circuit breaker is in the closed state, there will be a voice prompt of "Please open the circuit breaker" until the circuit breaker is opened;
When the handcart is not in the test position or working position, if the grounding switch is forced to close by mistake, there will be a voice prompt of "Please disconnect the grounding switch" until the grounding switch is opened;
When the circuit breaker is closed and the handcart is not in the test position or working position, if the grounding knife switch is forced to close by mistake, there will be a voice prompt of "Please disconnect the circuit breaker, please disconnect the grounding switch";
When the device is powered on, there will be a voice prompt "This circuit is live, do not approach it";
When the device is powered on and the three-phase high voltage is charged, there will be a voice prompt of "This circuit is live, do not approach it".
Installation Method
1. Installation methods of digital and common switch status indicators:
This product is panel-mounted, and its standard accessories are: temperature and humidity sensor, temperature and humidity sensor cable, mounting bracket, green terminal, etc. When installing, you only need to make holes on the panel of the switch cabinet. The size of the opening of the switch cabinet is 182mm¡Á125mm. To insert the device into the opening, you only need to use three mounting brackets to fit into the fixing holes of the device and then tighten, and tighten the screws.
3. Sensor installation method
(1) Use 35mm rail type installation or fix with screws.
(2) Fixed installation (hole spacing 37mm, hole diameter 4mm).
(3) The connection of the temperature and humidity sensor is connected by a USB interface plug-in.
Terminal Wiring Diagram Of Switch Status Indicator
Wiring instructions:
(1) The power supply terminals of the device are 22 and 23, and the voltage is AC/DC220V or 110V¡À10%; the heater output of the device is a passive relay contact output, and the heating power supply is connected externally.
(2) The analog display terminals of the primary circuit are: 1-8, and all switching values are passive dry contacts. The above is the standard configuration of the device. The specific terminal definition will be changed according to the different order requirements of the user. The terminal definition on the back of the actual device shall prevail.
(3) The wiring method of the accessory temperature and humidity sensor line is: connect the USB plug-in connector to the temperature and humidity sensor terminal (1, ) of the device, and connect the other end to the matching temperature and humidity sensor probe.
(4) Others Connect the working power supply only after connecting the wires according to the terminal wiring diagram of the device and checking them correctly.
Applications
Product selection
product name
|
product model
|
basic function
|
remarks
|
Switch status
|
CHTK500
|
|
Primary circuit simulation diagram, circuit breaker position, working state of manual experiment, grounding switch position spring energy storage state, high voltage live indication, high voltage live locking and wet temperature control, + 50 with nuclear phase (power inspection) and + 50, + 50 with self-inspection
|
Open hole is 120mm * 180mm
|
The number of explicit
Switch status
|
CHTK500S
|
|
First circuit simulation diagram, circuit breaker position, working state of manual experiment, grounding switch position spring energy storage state, high voltage live indication, high voltage live lock, digital display and two temperature and humidity control, with nuclear phase (power check) and + 50, with self-inspection and + 50
|
Open hole is 120mm * 180mm
|