Single-channel electrical fire monitor
Basic Functions
The type electrical fire monitoring detector can realize real-time monitoring and collection of the residual current and temperature value of the controlled circuit, and will send out an audible and visual fault alarm signal when the fault alarm data of the detection circuit is collected; it can also be networked with the electrical fire monitoring host, and the monitoring host can Judging the state of the on-site detectors, the host computer analyzes and processes to indicate the fault alarm type of a certain circuit, and sends out an audible and visual fault alarm signal.
The Main Technical Parameters
1. Rated working voltage: AC220V (AC85V-260V)
2. Residual current alarm range: 50-1000mA
3. Temperature alarm range: 25-125¡æ
4. Protection action time: ¡Ü0.5s
5. Alarm sound: 70db
6. Alarm output: switch type, contact capacity AC250V /3A
7. Communication method and distance: two-bus communication protocol/¡Ü1500m
8. Protection level: IP 30
9. Executive standard: GB14287.2-2014
10. Environmental conditions for use: Ambient temperature: 0¡æ¡«£«60¡æ
Relative humidity: 10%¡«90%
Type D Installation And Dimensions
Type D Wiring Schematic Diagram
1.Terminal diagram
2.Application Diagram
Note: The three-phase four-wire must pass through the transformer from the same direction
Type S Installation and Dimensions
Type S Wiring Schematic Diagram
1.Terminal diagram
2.Application Diagram
Product selection
product name
|
product model
|
basic function
|
remarks
|
Electric
fire monitoring and control device
|
CHTK888D
|
|
Function: digital display, detection
of residual current,
temperature, fire input, communication, alarm, tripping,
etc.
A is leakage; T is temperature; K is buckle
|
Al/T4
|
90mm*55mm*44mm
|