Citation Standards and Rules |
GB/T13850-1998 |
|
Input overrange |
Continuous: 1.2 times; Instantaneous: current 10 times (5 seconds), voltage 2 times (10 seconds) |
|
Enter frequency |
50/60Hz¡À10% |
|
Insulation strength |
AC 2kV |
|
Isolation withstand voltage |
Between standard input and output: AC 1KV; power supply and input, power supply and output: AC 2KV |
|
Insulation resistance |
¡Ý1000 |
|
Output ripple |
Basic error value not greater than 2 times |
|
Working conditions |
Ambient temperature: -10~+55¡æ, relative humidity ¡Ü93%,
No corrosive gas place, altitude ¡Ü2500mm
|
|
Storage conditions |
Temperature -40~+70¡æ, relative humidity 20~+99¡æ, no condensation |
|
MTBF |
¡Ý50000h |
|
Note: The nominal value of input signal 0~100% generally corresponds to the output of 4~20mA (special circumstances will be specified separately). |
Product name |
Input mode |
Output Settings |
illustrate |
Auxiliary power |
|||
4-AC |
5-AC |
Analog quantity |
Digital quantity |
Energy pulse |
|||
One way
Current, Voltage
Transmitter
|
¡ñ |
¡ñ |
1 way |
AC¡¢DC
80~270V
|
|||
¡ñ |
¡ñ |
1 way |
|||||
¡ñ |
2 way |
2 in 2 out or 1 in 2 out, isolated from each other |
|||||
¡ñ |
2 way |
||||||
¡ñ |
1 way |
True RMS measurement |
|||||
¡ñ |
1 way |
||||||
¡ñ |
¡ñ |
¡Ì |
Digital transmission |
||||
¡ñ |
¡ñ |
¡Ì |
|||||
¡ñ |
1 way |
External low-voltage DC power supply is required |
DC 12V
or 24V
|
||||
¡ñ |
1 way |
||||||
Three-way current transducer |
¡ñ |
3 way |
AC¡¢DC
80~270V
|
||||
Three way voltage transmitter |
¡ñ |
3 way |
|||||
Power Transmitter |
¡ñ |
1 way |
Three-phase three-wire |
||||
¡ñ |
1 way |
||||||
¡ñ |
1 way |
Three-phase four-wire |
|||||
¡ñ |
1 way |
||||||
¡ñ |
4 way |
¡Ì |
|||||
frequency transmitter |
¡ñ |
1 way |
|||||
¡ñ |
¡Ì |
||||||
Power Factor Transmitter |
¡ñ |
1 way |
|||||
¡ñ |
¡Ì |
||||||
Power factor
Angle transmitter
|
¡ñ |
1 way |
|||||
¡ñ |
¡Ì |
||||||
Comprehensive power transmitter |
¡ñ |
4 way |
¡Ì |
2 way |
Combined transmission |
||
Note: ¡ñ indicates that there is this input method: ¡Ì indicates that there is RS-485 interface digital output function. |
Specification Model Indicator |
BS41 |
BS51 |
BS4U |
BS5U |
||
Accuracy class |
0.2 level 0.5 level |
|||||
Input |
Nominal |
1A¡¢5A etc |
20mA etc |
100v¡¢220V¡¢380V etc |
75mV etc |
|
frequency |
50/60Hz¡À10% |
|||||
Output |
Aanalog quantity |
Nominal |
0~20mA¡¢4~20mA¡¢0~5V etc |
|||
Load Resistance |
Current output: RL<1k¦¸; voltage output: RL¡Ý5k¦¸ |
|||||
Digital quantity |
RS-485 interface MODBUS-RTU protocol; baud rate: default 4800 (optional 2400, 9600) bps |
|||||
Power supply |
Auxiliary power |
Ac¡¢DC 80~270v |
||||
Power dissipation |
¡Ü3.5VA |
Specification
Model Indicator
|
BS413 |
BS4U3 |
|
Accuracy class |
Level 0.5, Level 0.2 (True RMS input) | ||
Input |
Nominal input |
AC1A, 5A, etc. |
AC100V, 220V, 380V, etc. |
Output |
Analog output |
Simultaneously la, lb, lc three quantities |
Simultaneously Uab, Ubc, Uca or Uan, Ubn, Ucn three quantities |
Rated value |
4~20mA, 4~12~20mA, 0~5V, etc. | ||
Load Resistance |
Voltage output RL>100K¦¸, current output RL<510K¦¸ | ||
Power supply |
Auxiliary power |
AC/DC 80V~270V | |
Power dissipation |
<5VA | ||
Communication output |
Optional RS485 interface, MODBUS-RTU protocol, baud rate: default 4800 (optional 2400, 9600) bps |
Installed on a 35mm standard guide rail or fixed on the cabinet with screws.
Wiring method
product name |
product model |
basic function |
remarks |
|
AC current transmitter |
CHTK600-BS4I |
Single-phase current, single-phase voltage transmitter Can measure the current and voltage signals, After signal processing and isolation in DC flow Or voltage analog signal output.This transmitter Power supply to switch power supply, can work well in the grid fluctuating environment. |
Length * width * height of 92mm * 23mm * 135mm respectively |
|
DC electric current transmitter |
CHTK600-BS5I |
|||
AC voltage transmitter |
CHTK600-BS4U |
|||
DC electric voltage transmitter |
CHTK600-BS5U |
|||
AC current transmitter |
CHTK700-BS4I |
Can measure the current and voltage signals, After signal processing and isolation in DC flow Or voltage analog signal output. Export type single phase current, single phase voltage transmitter |
Length: * width: * height: 75mm: * 55mm: * 120mm |
|
DC electric current transmitter |
CHTK700-BS5I |
|||
AC voltage transmitter |
CHTK700-BS4U |
|||
DC electric voltage transmitter |
CHTK700-BS5U |
|||
Three-way AC current transmitter |
CHTK600-BS4I3 |
Three-way current and voltage combination transmitter Three-phase AC current and voltage transmitter is an instrument that can convert the measured three-phase AC current or voltage into the mainstream conversion output in a linear proportion. With the corresponding indicator instrument or equipment, the current measurement and control or voltage can be realized in the power system AC circuit. |
Length, * width, * height, 110mm * 75mm * 120mm |
|
Three-way AC voltage transmitter |
CHTK600-BS4U3 |
|||
Frequency transmitter |
CHTK600-BS4F |
|
A frequency transmitter is an instrument that converts the measured frequency signal into a DC current or voltage for isolating the converted output in a linear scale. |
Length: * width: * height: 75mm: * 55mm: * 120mm |
Power factor transmitter |
CHTK600-BS4H |
A power factor transmitter is an instrument that converts the measured power factor signal into a converted output DC current or voltage in a linear scale |
||
Active power transmitter |
CHTK600-BS4P |
The power transmitter will input three-phase three lines or three-phase four lines of voltage and current signals into the success rate of linear transmission output DC current or voltage instrument |
Length, * width, * height, 110mm * 75mm * 120mm |
|
Reactive power transmitter |
CHTK600-BS4Q |