Input Specifications
Code
|
Input signal
|
Distribution voltage
|
1
|
4-20mA field two-wire
transmitter
|
24V
|
Output Specifications
Code
|
Output signal
|
Output impedance
|
1
|
0-2V
|
¡Ý10K
|
2
|
0-5V
|
3
|
0-10V
|
4
|
1-5V
|
5
|
0-10mA
|
¡Ü1K
|
6
|
0-20mA
|
¡Ü500¦¸
|
7
|
4-20mA
|
8
|
User specified parameter
|
LP
|
Input surge protection
|
In: 5KA Imax: 10KA
|
Features
¡ñPower & alarm LED
¡ñInput surge protection
¡ñProgrammable input & output ranges
¡ñThree isolations (input/output/power)
Model Selection Examples
Technical Index
Distribution voltage: 24V (30mA max drive current)
Output load: 0-500¦¸
Response time: <0.05s (0~90%) (TYP)
Ripple: <10mVrms
Transmission errors: 0.1% of the final value
Temperature coefficient: Measured value of
15ppm/K/a load of 100¦¸
Compressive strength: 100M¦¸+ for 1500VAC/min
under the condition of 2500VDC
Electromagnetic compatibility: Conforms to
GB/T18268 industry equipment application
requirement (equivalent to IEC61326-1)
Operation temperature: -25¡æ~+85¡æ
Operation humidity: <90%RH (no condensate water)
Power: 24VDC¡À10%
Consumption power: <1W
Housing material: Flame retardant for ABS
Weight: about 90g
Dimensions: 12.5x106x112mm (TxWxH)
Surge Protection Feature (Models With -LP)
Max continuous operation voltage: 30VDC
Rated discharge current: In£º5KA (line to ground,line to line)
Max discharge current Imax: 10KA (line to ground)
Standard: GB/T18802.21-2004
Notes For Surge Protection Wiring
1£® The 6 pin terminal of the instrument must be grounding under surge protection
2£® Adopt separable wiring terminal for user convenience
3£® Wire cross-section area around 0.5mm²¡«2.5mm²
4£® 8mm bare wire, tighten with M3 screw
Wiring Diagram
Application Case