Main Functions And Features
♂Integrate intelligent temperature transmitter, isolator and power distribution in one body
♂ "Input-Output 1-Output 2-Power" four isolated
♂Software nonlinear correction, input and output high linearity conversion
♂Software auto-zero, eliminating errors caused by temperature drift and time drift
♂Users can set the signal range and signal type through PC8800
♂Can be installed in high density
Machine Specifications
Structure: Small snap-fit structure
Connection method: pluggable terminal block
Terminal screw material: nickel-plated iron surface
(The allowable torque of the screw is less than 0.8N•m)
Shell material: polyphenylene ether, high heat resistance, flame retardant, high strength electrical properties, wear-resistant, non-toxic,
Pollution resistance and other advantages.
Isolation: channel insulation (input-output-power supply)
Power indicator light: green LED, light up when power supply
Alarm indicator: red LED, input disconnection or abnormal flashing
Output Parameters
♂Output current
Output range: 4~20mA
Allowable range: ≒250次
Output range: 0~10mA
Allowable range: ≒500次
♂Output voltage
Output range: 1~5V
Allowable range: ≡250K次
Output range: 0~10v
Allowable range: ≡500K次
♂On-site power supply
Distribution voltage: 22~26V
Distribution current: short circuit protection, single 30mA, dual 60mA
Environmental Parameters
Power supply: 1~4W 85~265V.AC or 22~28V.DC
Operating temperature range: 0~60⊥
Operating humidity range: 0~90%RH (non-condensing)
Installation: DIN35mm rail installation
Dimensions: 13*114*116(W*H*D)
Weight: about 100g
Performance Index (Relative To Full Scale)
Standard accuracy: ㊣0.1%/㊣0.2% at 25∼C
Cold compensation accuracy: ㊣2⊥ K E
Temperature coefficient: ㊣0.015%/⊥
Response time: ≒0.5s (0↙90%)
Influence of power supply voltage variation: ≒0.1%/allowable voltage range
Insulation resistance: between input-output-power supply
Above 10OM次/DC500v
Isolation Strength: Between Input-Output-Power-Ground
DC1000v 1 minute
AC1000v 1 minute
Effect of load resistance change: ㊣0.1%/250次
Power-on stabilization time: ≒3s
Front View
Side View
Application Guide & Terminal Wiring Diagram
Application Case Diagram