Loading...

  •  

Ultra-thin signal isolator type A


Input Specifications


Code

Input signal

Distribution voltage

1

4-20mA field two-wire
transmitter

24V


Output Specifications

Code

Output signal

Output impedance

1

0-2V

¡Ý10K

2

0-5V

3

0-10V

4

1-5V

5

0-10mA

¡Ü1K

6

0-20mA

¡Ü500¦¸

7

4-20mA

8

User specified parameter

LP Input surge protection In: 5KA Imax: 10KA


Features

¡ñPower & alarm LED
¡ñInput surge protection
¡ñProgrammable input & output ranges
¡ñThree isolations (input/output/power)

Model Selection Examples


Technical Index

Distribution voltage: 24V (30mA max drive current)
Output load: 0-500¦¸
Response time: <0.05s (0~90%) (TYP)
Ripple: <10mVrms
Transmission errors: 0.1% of the final value
Temperature coefficient: Measured value of
15ppm/K/a load of 100¦¸
Compressive strength: 100M¦¸+ for 1500VAC/min
under the condition of 2500VDC
Electromagnetic compatibility: Conforms to
GB/T18268 industry equipment application
requirement (equivalent to IEC61326-1)
Operation temperature: -25¡æ~+85¡æ
Operation humidity: <90%RH (no condensate water)
Power: 24VDC¡À10%
Consumption power: <1W
Housing material: Flame retardant for ABS
Weight: about 90g
Dimensions: 12.5x106x112mm (TxWxH)

Surge Protection Feature (Models With -LP)

Max continuous operation voltage: 30VDC
Rated discharge current: In£º5KA (line to ground,line to line)
Max discharge current Imax: 10KA (line to ground)
Standard: GB/T18802.21-2004

Notes For Surge Protection Wiring

1£® The 6 pin terminal of the instrument must be grounding under surge protection
2£® Adopt separable wiring terminal for user convenience
3£® Wire cross-section area around 0.5mm²¡«2.5mm²
4£® 8mm bare wire, tighten with M3 screw

Wiring Diagram



Application Case


Online Message

*
*
*

Related Products

See More