Loading...

|
Work |
Temperature range |
-10~+55¡ãC |
|
Relative humidity |
45-80% for a short time 95% non-condensing |
|
|
Atmospheric pressure |
80-110kpa |
|
|
Altitude |
<2000m |
|
|
Storage and transportation |
Temperature range |
-40~+75¡ãC |
|
DC power supply |
Rated voltage |
220VDC£¨110V£© |
|
Permissible range |
100£250V |
|
|
AC power |
Rated voltage |
220VAC |
|
Permissible range |
150£250V |
|
|
Power consumption |
The normal |
<3W/VA |
|
Action |
<10W/VA |
|
|
Power drop |
50% |
1s |
|
0% |
100ms |
|
Electric current |
Rated current In |
5A£¨1A£© |
|
|
Power consumption |
<0.5VA |
||
|
Heat stable |
Continuous |
20A |
|
|
1s |
100A |
||
|
Dynamic stabilization |
10ms |
250A |
|
|
Voltage |
Rated voltage Un |
100V |
|
|
Ultimate voltage |
200V |
||
|
Power consumption |
<0.3VA |
||
|
Parameter name |
Measuring range |
Error |
Power dissipation |
|
Three-phase voltage UAB, UBC, UCA |
10¡129V£¨xPT£© |
<=0.5% |
<=0.3VA |
|
Three-phase current la, lb, lc |
0.2¡6A£¨xCT£© |
<=0.5% |
<=0.3VA |
|
Power factor PF |
0.5L¡0.5C |
<=0.5% |
|
|
Passive contact signal input |
Number of signal inputs |
10 way |
|
The scope of work |
24V DC (self-produced by the device) |
|
|
Consumption power |
<0.3W |
|
|
Resolution |
2ms |
Pulse frequency<100Hz |
|
Package dimensions |
(H)/(W)/(D)mm (for reference only) |
|
Device size |
(H)/(W)/(D)mm (for reference only) |
|
Device weight |
Approx. kgmm (for reference only) |
|
Shell material |
Aluminum profile structure |
|
Degree of protection |
IP5SNI |
|
Installation method |
Embedded or tiled, top-impact fixed |
|
Maximum Switching Voltage |
250V AC/30VDC |
|
Maximum switching current |
8A |
|
Maximum Switching Power |
1250VA/150W |
|
Output contact capacity |
<250V, 1A (inductive load), disconnection capacity <50W |
|
Specified load |
5A 250V AC/30V DC |
|
Dielectric withstand voltage |
4000VAC |
|
Insulation resistance |
1000M¦¸ |
|
Logging Event Type |
Fault, over limit, switch displacement, external tripping, modification of fixed value |
|
|
Number of recorded events |
30 |
Power-down retention |
|
Record event content |
Year, month, day time scale, event type details |
|
|
Time resolution |
2 ms |
|
|
Event query method |
Far away |
Communication call |
|
On the spot |
Button menu LCD display |
|
|
Electrical Specifications (Isolated RS485) |
Number of communication nodes |
64 |
|
Transmission rate |
4800¡9600 Buad |
|
|
Transmission distance (9600Buad) |
1000m |
|
|
Connector |
Terminal output |
|
|
|
IEC60870-5-103 |
8 data bits, 1 stop bit, even parity |
|
Insulation test |
Insulation resistance |
2kv50Hz1minute |
|
Power frequency withstand voltage IEC60-2 |
50M¦¸ |
|
|
Damp heat test IEC60-2-30 |
50M¦¸ 1.5kV |
|
|
Shock withstand voltage test |
Switch value input circuit to ground |
¡À5kV |
|
Other circuit IEC255-5 |
¡À5kV |
|
|
Mechanical shock test |
Test position |
Triaxial |
|
Test frequency range |
10¡150Hz |
|
|
Crossover Frequency |
f¡Ü60Hz; fixed amplitude 0.075mm |
|
|
Number of sweep cycles per axis |
f>60Hz; constant acceleration 10m |
|
|
IEC255-21 |
10/S2 |
|
Anti-high frequency interference test IEC255-22-1 1M attenuation shock wave |
Common Mode |
2.5kV |
|
Differential mode |
1.0kV |
|
|
Electrostatic discharge interference test Grade III IEC6100-4-2 |
Contact |
6.0kV |
|
Air |
8.0kV |
|
|
Radiated electromagnetic field interference test EN55011 |
Strength of the test field |
|
|
Scanning frequency |
150kHz¡80MHz |
|
|
Radio Frequency Interference Test |
Directly referenced in a common mode£¨IEC6100-4-6£© |
10V/m(rms) f=150kHz¡80MHz |
|
in a radiative manner quote £¨IEC6100-4-6£© |
10V/m(rms) f=80Hz¡1000MHz |
|
|
Fast Transient Tests IEC255-4 |
Common Mode Voltage Peak Pulse frequency Duration of each polarity |
2kV 4kV |
|
5kz 2.5kz |
||
|
10min |
||
|
Surge lightning test IEC6100-4-5 |
Power supply, AC, DC inlet |
4KV Common mode |
|
2KV Differential mode |
||
|
I/O Entrance |
2KV Common mode |
|
|
1KV Differential mode |